This guide is for installers configuring a Sungrow Logger 1000 (EU) so Octave’s EMS can perform solar curtailment (and other active power services) via Modbus TCP.
</aside>
Prerequisites
- SmartLogger 1000 is powered on and connected to the network.
- Your laptop/PC is on the same network as the SmartLogger.
- Web browser (Chrome / Edge / Firefox).
- Installer / O&M credentials.
- Network access to Modbus TCP port 502.
Configure SmartLogger for remote active power control
-
Open a browser and go to the SmartLogger WebUI:
http://<SmartLogger-IP>
-
Log in with an installer / administrator account.
-
In the left menu, navigate to Power control → Active power.
-
Under Active power control mode, set:
Remote power control

-
Configure the following parameters and Save:
| Parameter |
Value |
| Control strategy |
Open-loop control |
| Query recovery time |
1 s |
| Frame delay |
18 ms |

Verify Modbus TCP connectivity (port 502)
- Sungrow SmartLogger uses Modbus TCP on port 502 by default.
- Ensure:
- Port 502 is open on the network path between Octave / site network and the SmartLogger.
- No firewall blocks inbound Modbus TCP requests.
Find the Device Communication ID (required)
- In the left menu, open Device maintenance → Device list.