<aside>
🔧
This guide is for installers enabling Modbus TCP and configuring RRCR (Remote Power Reduction Control) on a SolarEdge inverter using the SolarEdge Installer App.
</aside>
Prerequisites
- SolarEdge Installer App installed and you can access the site (existing commissioned system).
- Installer credentials / permissions for the inverter.
- The inverter is reachable (remote access may briefly interrupt production).
- You have a plan for static IP addressing and you can verify the inverter is online (e.g., IP scanner).
1) Connect to an existing system
-
Open the SolarEdge Installer App.
-
On the home screen, select Connect → Existing system.
This allows access to an already-commissioned site.

2) Open the inverter from Inventory
- Go to Inventory.
- Select the correct inverter.
- Confirm you see:
- Manufacturer: SolarEdge
- A recent Last Measurement timestamp

3) Start Remote Access
- Scroll down on the inverter page and tap Remote Access.
- Press Connect and accept the warning.