1. Log in
- Access the local web user interface of the SmartLogger.
- Use an Installer account.

2. Enable Modbus TCP Server
- Go to
Settings → Modbus TCP (left-side menu).
- Fill in the fields as shown below:

3. Activate Power Control Mode (Logger Level)
- Go to
Settings.
- Select
Active Power Control from the left-side menu.
- Enter the values as shown below:

4. Configure Each Individual Inverter
- Go to
Monitoring.
- Select
Inverters(left-side menu).
- Provide the number of inverters connected to the Logger (e.g. 3 in the example below)
- For each inverter:
- Provide the Model name to Octave (e.g. SUN2000-100KTL-M1 in the case below)
- Go to running parameters and then select power adjustment
- Ensure that it has
Remote comunication Schedulingset to Enabled
- Set the active power change gradient to 125.000
- below the screen choose batch configuration and select all inverters and confirm
- this will apply the configuration to all inverters allowing the steering of individual inverter